اسم المعدة الاسم التجاري رقم الموديل بلد الصنع رقم شهادة السلامة العالمية نوع المختبر الفاحص
غطاء معوق للحريق - الغطاء المنتفخ Knauf Putty Pads Putty Pads KL/PF 60-01 fire resistance 60 minutes Putty Pads KL/PF 120-01 Fire resistance 120 minutes Knauf putty pads are blue sheets of intumescent, moldable putty designed for used inside metallic electrical sockete boxes for the purpose of fire protection. the putty pads are available in 170mm x 170mm and 230mm x 170mm sizes , both 3mm thick. standard test method : ASTM E 814-13 A WHI18-22825431 INTERTEK TESTING SERVICE, USA
أنظمة جدار KNAUF 1 hr. Fire Rated Non-loadbearing wall assembly Model: Knauf 12.5mm RG-X Gypsum Boards Design Number: KL/GBF 60-14 Minimum thickness of the wall - 100mm Integrity: 60 minutes Radiation: 60 minutes Insulation: 60 minutes WHI24-22825438 INTERTEK TESTING SERVICE, USA
أنظمة جدار KNAUF 12.5 mm Aquapanel Cement Board Outdoor and 12.7 mm GW-TX Gypsum board wall assembly The asymmetrical, 3050 x 3050 mm (10 ft x 10 ft), non-load bearing wall was constructed of steel studs, gypsum board, insulation, and cement board. KL/GBF 120-12 ASTM E119- 120 minutes WHI18-22825423 INTERTEK TESTING SERVICE, USA
أنظمة جدار 12.5mm FM DFH1 12.5mm FM DFH1 12.5mm FR DF A 3000mm x 3000mm, non-load-bearing wall was constructed of galvanized steel track, and two layers of 12.5mm FM DFH1 & FR DF boards on each side of the framing members. Integrity - 120 minutes Insulation - 120 minutes WHI23-22825435 INTERTEK TESTING SERVICE, USA
أنظمة جدار 1 1/2 hr. Fire Rated Non-loadbearing wall assembly 1 1/2 hr. Fire Rated Non-loadbearing wall assembly Model: Knauf 12.5mm RG-X Gypsum Boards Design Number: KL/GBF 60-15 Knauf Regular Gypsum X Boards (RG-X) (density >=592 kg/m?) on both sides of a framing system made of GI studs and tracks infilled with 50mm layer of glass mineral wool insulation (density-16 kg/m?). Minimum thickness of the wall - 100mm. WHI24-22825439 INTERTEK TESTING SERVICE, USA
أنظمة جدار Fire rated Non Load Bearing Wall Assembly 60 min Fire rated Non Load Bearing Wall Assembly 60 min Model: Knauf 12.5mm RG gypsum boards Design number: KL/GBF 60-09 Density >=592kg/m? Minimum thickness of the wall - 100mm الإمارات العربية المتحدة WHI1622825415 INTERTEK TESTING SERVICE, USA
أنظمة جدار 1 1/2 hr Fire Rated Non-Loadbearing wall assembly 1 1/2 hr. fire rated non loadbearing wall assembly KNAUF 12.5 FR W112 SYSTEM Design number : KL-GBF 90-01 Dry wall partitions are made of 2 layers of 12.5mm knauf FR gypsum board on both sides of a framing system made of GI studs and tracks. Intergraty - 103 minutes Insulation 92 minutes الإمارات العربية المتحدة WHI15 -22825413 INTERTEK TESTING SERVICE, USA
أنظمة جدار Non-combustible Floor /ceiling Assembly Type X Gypsum Board-Non Combustible Floor/ceiling Assembly 12.7 mm thick knauf GW-TX Gypsum boards Design Model Number : KL-GBF 60-03 ASTM E119- rating 60 minutes. Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار Partition Wall,Non -Loadbearing wall Assembly TYPE X-Partition wall, Non Loadbearing wall Assembly Type X Gypsum board Design model Number KL-GBF 60-04 Design Model number KL-GBF 60-02 Fire resistance test 1 hr Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf GW-TX and DH-H1 Non -Loadbearing wall Assembly KNAUF GW-TX, DH-H1 non-loadbearing wall Assembly Design model no: KL/GBF 120-02 Fire resistance test 2 (two) hours Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار KNAUFGW-TX,Knauf Head of wall Joint KNAUFGW-TX, knauf Head of wall Joint Design model no: KL/GBF 60-01 fire resistance test: 1 (one) hour Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار Partition Wall,Non-Load Bearing Wall Assembly Partition Wall, Non Loadbearing wall Assembly Type X Gypsum board design model no KL/GBF 120-05: Fire rating 120 minutes design model no KL/GBF 120-06: Fire rating 120 minutes Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار KNAUF GW-TX and DH-H1,Knauf Head of wall joint Knauf GW-TX and DH-H1, Knauf head of wall joint Design model no: KL/GBF 120-03 fire resistance test: 2 (two) hours Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted الإمارات العربية المتحدة WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار 2 hrs Fire Rated Non Loadbearing wall assembly 2 Hrs. Fire Rated Non-load bearing wall assembly KNAUF 15 FR W112 System Design model no: KL/GBF 120-07 fire resistance rating Integrity: 129 minutes Insulation: 122 minutes الإمارات العربية المتحدة WHI15-22825414 INTERTEK TESTING SERVICE, USA
أنظمة جدار 1 hr fire Rated Non -Loadbearing wall assembly 1 hr. Fire Rated Non-Loadbearing wall assembly KNAUF 12.5RG W112 SYSTEM Design model no: KL/GBF 60-05 fire resistance rating Integrity: 80 minutes Insulation: 73 minutes Model: Knauf regular gypsum board (RG) Knauf mold and moisture Resistant gypsum board (MMR) الإمارات العربية المتحدة WH15 -22825412 INTERTEK TESTING SERVICE, USA
أنظمة جدار Non Load bearing wall assembly -E119-120 Minutes 12.5mm Aqua panel cement board indoor ,one layer of 12.7mm GW-TX behind Aqua panel, insulation and two layers of 12.7 mm GW-TX Type -X gypsum board model ASTME119- rating: 2 hours Design no: KL/GBF 120-11 The asymmetrical, 3050 x 3050 mm (10 ft x 10 ft), non-load-bearing wall was constructed of steel studs, gypsum board, insulation, and cement board. WHI17-22825421 INTERTEK TESTING SERVICE, USA
أنظمة جدار 12.5MM , FM, FR, Pro HD Board Wall Assembly 12.5mm FM, RF or Pro HD Board Wall Assembly 1-2 Hours Design model no: KL/GBF 120-09 fire resistance rating Integrity: 126 minutes Insulation: 120 minutes A 3000mm x 3000mm, non-load-bearing wall was constructed of galvanized steel studs, galvanized steel track, and two layers of 12.5 mm FM Boards on each side of the framing members. EN 1364-1(2015) الإمارات العربية المتحدة WHI1622825427 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf Fire Rated Access Panel Knauf Fire Rated Access Panel modified BS 476 part 22 Integrity rating 60 minutes The panel frame are made from 1.2 mm thick GI sheet metal, with the powder coating finish. Two layers of GW-TX type x 12.7 mm gypsum board are fitted within the access panel to improve the panel's fine resistance. WHI18-22825422 INTERTEK TESTING SERVICE, USA
أنظمة جدار Non Load bearing wall assembly 12.5mm Aqua panel cement board outdoor ,insulation and 1 layer of 15.9mm GW -TX Type -X Gypsum Board The 18 ft high x 14 ft wide ISMA test wall was constructed by representative for Knauf LLC. The assembly consisted of metal studs, gypsum board interior cladding, insulation batts, a moisture barrier, and cementitious exterior sheathing. KL/GBF 30-02 WHI17-22825420 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf KCUA-A116 Cinema Wall Model No: KL/GBF 180-03 fire resistance 180 mins Knauf type x fire rated gypsum wall board (GW-TX) are 3600 x 1200 x 15.9mm (w x h x thick), used as non-load bearing triple layered gypsum board partition wall. The 3 hours system has been tested in accordance with ASTM E119. The system is constructed of Triple layers of 15.9 mm thick Knauf type x fire rated gypsum wall board (GW-TX), mounted on both exposed & unexposed face of the framing system. ASTM E119(2014) & ASTM E2226-12, NFPA 251, UL 263 WHI15-22825411 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf 15mm FM, FR, or Pro HD Wall Lining - 2 hours - En 1364-1 Design Model Number KL/GBF 120-13 Integrity - 125 minutes Insulation - 57 minutes Knauf fire & moisture resistant gypsum board (FM)- 1200 x 2400 x 15 mm thick Knauf fire resistant gypsum board (FR)- 1200 x 2400 x 15 mm thick Knauf pro HD- 1200 x 2400 x 15 mm thick Knauf pro Acoustik- 1200 x 2400 x 15 mm thick Maximum Height - 4m Maximum Width - Infinite WHI21-22825430 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf Knauf GW-TX & DH-H1 Model No: KL/GBF 120-02 Fire resistance 120mins Head of wall joint constructed - (4) 2-1/2" wide pieces - 15.9 mm thick Head of wall width: 63.5 mm Total thickness: 63.6 mm Length: unrestricted WHI15-22825401 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf AQUAPANEL? Cement Board Indoor? 3 hours ? ASTM E2307 Mode No: KL/BPF 180-1 Fire resistance 3 hours Density: 1050 kg/m? Thickness: 12.5mm WHI21-22825432 INTERTEK TESTING SERVICE, USA
أنظمة جدار Non - Load Bearing Floor/Ceiling Assembly Non- Load Bearing Floor/Ceiling Assembly Certified product: 60 minutes fire rated floor/ceiling assembly Model: 12.7mm thick, Knauf GW-TX gypsum boards density > 600 kg/m? KL/GBF 60-03 ASTM E119-12a الإمارات العربية المتحدة WHI16 22825417 INTERTEK TESTING SERVICE, USA
أنظمة جدار Knauf Knauf steel Protekt Board system KL/BI 120-1 fire resistance 120 minutes Structural steel beams are protected with Two or three layers of 12.5mm or 15mm thick FR boards with box-type protection on the bottom and sides of the beams using a clip and channel system. WHI22-22825433 INTERTEK TESTING SERVICE, USA
أنظمة جدار Non-Load Bearing Floor/Ceiling Assembly Non load bearing Floor/Ceiling Assembly 120 min Model No KL/GBF120-08 15.9mm thick, knauf GW-TX gypsum boards The base layer was secured using Knauf TN 3.5 x 25 self-drilling screws spaced 8" (203mm) o.c. density > 600 kg/m? ASTM E119-12a الإمارات العربية المتحدة WHI 1622825418 INTERTEK TESTING SERVICE, USA
أنظمة جدار Fire rated Non- Load Bearing Wall Assembly 60 min Fire Rated Non Load Bearing Wall Assembly 60 Min Model: Knauf 15mm FM Gypsum Boards Non-Load Bearing Wall Assembly made of 1 layer of 15mm Knauf fire & Moisture resistant (FM) gypsum boards Density>= 584 kg/ m? on both sides of a framework made of GI studs and tracks infilled with 50mm layer of glass mineral wool insulation (density-16 kg/m?). Minimum thickness of the wall-80mm KL/GBF 60-10 الإمارات العربية المتحدة WHI1622825416 INTERTEK TESTING SERVICE, USA
أنظمة جدار 15mm FM,FR, Pro HD board Shaftwall Assembly 15mm FM,FM, Pro HD Board Shaft wall Assembly A 3000mm x 3000mm, non-load bearing asymmetrical wall was constructed of galvanized steel studs, galvanized steel track, 2 layers of 15 mm FM Boards, and a single layer of 25mm core board. Fire rating - FM, FR, pro HD and pro acoustik board exposed: Integrity - 120 minutes Insulation - 73 minutes Fire ratings - core board exposed Integrity - 138 minutes Insulation - 135 minutes الإمارات العربية المتحدة WHI16 22825428 INTERTEK TESTING SERVICE, USA
أنظمة جدار 12.5mm Regular Plus A 12.5mm Regular Plus A A 3000mm x 3000mm, non-load-bearing wall was constructed of galvanized steel studs, galvanized steel track, and two layers of 12.5mm Regular Plus A boards on each side of the framing members. WHI23-22825434 INTERTEK TESTING SERVICE, USA